The transmitters are constructed around a temperature element providing a signal proportional to the temperature. The built-in electronics convert the measurement signal to an output signal 0...10 V DC or 4...20 mA.
Supply voltage The transmitters can be powered either with 24 V AC or 18...35 V DC (0...10 V models), or 11...30 V DC (4...20 mA models). The transmitters will automatically adapt to the supply voltage.
Immersion well The transmitter is supplied with a nickel plated brass/ copper well with a R 1/2” connection.
Short facts about TLT...(-420) • Excellent long-term stability • Wide measurement range • Output signal 0...10 V DC or 4...20 mA • Supply voltage 24 V AC or 15...35 V DC • Protection class IP65
Model |
Supply voltage |
Unit range |
Output signal
|
Measurement method
|
Mounting |
TLT100 |
18...24 V AC or 18...35 V DC |
0...100°C. |
0...10 V |
3-wire |
Immersion mounting |
TLT100-420 |
11...30 V DC |
0...100°C. |
4...20 mA |
2-wire |
Immersion mounting |
TLT50 |
18...24 V AC or 18...35 V DC |
-30...+50°C |
0...10 V |
3-wire |
Immersion mounting |
TLT50-420 |
11...30 V DC |
-30...+50°C |
4...20 mA |
2-wire |
Immersion mounting |