Product Description • Completely closed cell, physically crosslinked foam pipe insulation. • Heat bonded factory applied reinforced aluminium foil. • Pre-slit for faster installation. • Flexible, tough and durable. • Excellent compression resistance due to its crosslinked foam structure. • Superior insulating properties compared to other flexible closed cell foams. • Very high vapour diffusion resistance Class 1 Vapour Retarder under ASHRAE 2009. • No cladding required for internal applications • Conforms to ISO 5659-2 “Smoke Density and Toxicity”. • Anti-Microbial. • Green Star Compliant Product (VOC). • Complies to NFPA 90A & NFPA 90B. • Developed and Manufactured in Australia
Technical Data |
Material: Physically (irradiation) crosslinked polyolefin foam with factory applied reinforced foil. |
Density: |
Thermal Conductivity: (ASTM C518) |
Water Vapour Permeability: (ASTM E96) |
Water Vapour Permeance: Permeability Resistance Factor: |
Water Absorption by Volume: (JIS K 6767) |
Resistance to Fungi: (ASTM G21) |
Ozone Resistance : UV Resistance: |
Operating Temperature : |
25kg/m3 (foam core only) |
0.032 W/m/oK (@ 23°C mean temperature) |
8.19 X 10-15 kg/Pa.s.m (0.029 mg.m/N.h) |
3.3 X 10-4 g/MN.s μ>20,000 |
< 0.1% v/v (0.00038 g/cm2) Zero Growth |
Excellent Excellent |
-80° C to 100° C |
Fire and Smoke Behaviour |
BS 476 Part 6 & 7 Class 0 AS1530.3(1999) |
Spread of Flame Index: 0 |
Heat Evolved Index: 0 |
Ignitability Index: 0 |
Smoke Developed Index: 0-1 |
UL 94 HF-1 |
ASTM E 84 Complies to: |
Flame Spread Index |
FM 4924 Approved (up tp 12” IPS & 50mm wall thickness) |
NFPA 90A & NFPA 90B Complies with requirements ISO 5659-2 (1994) |
Smoke Density D |
< 200 |
Smoke Toxicity Satisfi max allowable |
concentrations for the following combustion gases CO, HCl, HBr, HF, HCN, NO , SO |
BS 6853 Annex B Complies to: Smoke Toxicity Index R <1.0 |
|